Kyoritsu KEW 4106 Earth Resistance & Resistivity Tester
Zoom image

Kyoritsu KEW 4106 Earth Resistance & Resistivity Tester


Not rated yet

High test current up to 80mA yielding resolution of 0.001on 2range.

Advanced Filtering method (based on FFT Fast Fourier Transform) reduces noise interference for obtaining stable measurements.

Automatic and Manual selection of the Test Current Frequency in four bands (94/105/111/128Hz). In Automatic mode, KEW 4106 will select the most suitable Frequency.

Several sub-results can be shown on the display: Resistance of the Auxiliary Earth Spikes, Frequency of Test Current, Voltage and Frequency of Interference (noise), Residual Resistance Rk, etc.

Warning for excessive noise and high Auxiliary Earth Spikes resistance.

Large Graphic Display with backlight for readings in poorly illuminated areas.

Up to 800 measurement results can be saved in the memory and recalled on the display.

The stored results can be transferred to a PC using the "KEW Report" software and a USB adaptor (Model 8212-USB) which are included.

Robust design with IP54 protection.

  • $0.00
Qty:  
In stock (1000 items available)
FunctionRangeResolutionMeasuring rangeAccuracy
Earth resistance
Re
(Rg at
measurement)
2/td>0.001/td>0.03 - 2.099/td>%rdg.03/td>
20/td>0.01/td>0.03 - 20.99/td>%rdgdgt (*1)
200/td>0.1/td>0.3 - 209.9/td>
2000/td>1/td>3 - 2099/td>
20k/td>10/td>0.03k - 20.99k/td>
200k/td>100/td>0.3k - 209.9k/td>
Auxiliary earth resistance
Rh, Rs



8% of Re+Rh+Rs
Earth resistivity
/th>
2/td>0.1m - 1
Autoranging
0.2 - 395.62aRg (*2)
20/td>0.2 - 3956
200/td>20 - 39.56k
2000/td>0.2 - 395.6k
20k/td>2.0 - 1999k
200k/td>
Series interference voltage
Ust (A.C only) (*3)
50V0.1V0 - 50.9Vrms%rdgdgt (50/60Hz)
%rdgdgt (40 - 500Hz)
Frequency
Fst
Autoranging0.1Hz
1Hz
40Hz - 500Hz%rdgdgt
Measuring methodEarth resistance: Fall-of-potential method
(currents and voltages measured via the Probes)
Measurement method of Earth Resistivity (: Wenner 4-pole method
Series interference voltage (earth voltage)
RMS Rectifier (between the E-S Terminals)
Memory capacity800 data
Communication InterfaceModel 8212-USB Optical Adaptor
LCDDot-matrix 19264 monochrome
Over-range Indication"OL"
Overload Protectionbetween E-S(P) and between E-H(C) terminals AC280V / 10 sec.
Applicable standardsIEC 61010-1 CAT III 300V, CAT IV 150V Pollution degree 2
IEC 61010-031, IEC 61557-1, 5, IEC 61326-1 (EMC), IEC 60529 (IP54)
Power sourceDC12V : sizeAA manganese dry battery (R6) 8
(Auto power off: approx. 5 minutes)
Dimensions167(L) 185(W) 89(D) mm
Weightapprox. 900g (including batteries)
Accessories7229A (Earth precision measurement),
7238A (Simplified measurement test leads),
8032 (Auxiliary earth spikes [2 spiks/set])2 sets (4 spikes in total),
8200-04 (Cord reel [4 pcs])1 set,
8212-USB (USB adaptor with "KEW Report(Software)"),
9121 (Shoulder strap),
9125 (Carrying case),
R6 8, Instruction manual, Calibration certificate
Optional8212-RS232C (RS232C adaptor with "KEW Report(Software)")

(*1) Auxiliary earth resistance is 100with Rk correction
(*2) Depending on the measured Rg. Interval [a] between auxiliary earth spikes is 1.0 - 30.0m
(*3) This instrument is NOT designed to measure line voltages on commercial powers.

    • SKU
      Kyoritsu KEW 4106
Customer reviews
Please sign in to add review
There are no comments yet. Be the first to leave a comment